Powerware 9315 User Manual

Page 36

Advertising
background image

INSTALLING A REMOTE BATTERY DISCONNECT

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201244 Rev E www.powerware.com

4-2

S

Nominal voltages listed in this chapter are for a lead‐acid batteries rated per NEC at
2.00 Vdc per cell.

S

Battery strings must be installed according to all applicable codes and regulations,
including NEC, Article 480.

S

The UPS to battery cable should be sized for a total maximum voltage drop
of 1% nominal DC Link voltage at maximum current.

S

Table 4‐1 details the power cable terminations.

S

The remote battery disconnect weighs approximately 60.3 kg (133 lb).
It has an ampere interrupting capacity (AIC) of 100,000 at 500 Vdc.

Table 4‐1. Remote Battery Disconnect Power Terminations

Number and Type of Accessories Permitted

Terminal

Terminal Function

Size of Termination

Tightening Torque

Nm (lb ft)

Bolt Size

E4 (+)

UPS Battery Input (+)

See Table H on page A-16

E5 (–)

UPS Battery Input (–)

See Table H on page A-16

Breaker (+)

Battery Disconnect (+)

8 – 1 Bolt Mounting

Bus Bar

76 (56)

1/2”

Breaker (–)

Battery Disconnect (–)

8 – 1 Bolt Mounting

Bus Bar

76 (56)

1/2”

Breaker (jumper)

Battery Disconnect

(jumper)

8 – 1 Bolt Mounting

Bus Bar

76 (56)

1/2”

Table 4‐2. Remote Battery Disconnect Circuit Breaker Ratings

UPS Model

Circuit Breaker Rating

DC Voltage

9315‐750/500

1600

384

9315‐750/625

2000

384

9315‐750/750

2500

384

Advertising