INSTALLATION REFERENCE

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201244 Rev E www.powerware.com

A-19

14. External overcurrent protection is not provided by this product, but is required

by codes. See Table E through Table G starting on page A-13 for wiring
requirements. If an output lockable disconnect is required, it is to be supplied
by designated personnel.

15. Table K lists the maximum rating for continuous duty rated input circuit

breakers.

C

A

U

T

I

O

N

To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current
ratings from Table K according to the NEC, ANSI/NFPA 70.

Table K. Maximum Input Circuit Breaker Ratings

UPS Model

Input Voltage Rating

400V

480V

600V

PW9315-625/400
PW9315-625/450

1000A

N/A

N/A

PW9315-625/500
PW9315-625/562

1200A

N/A

N/A

PW9315-750/500
PW9315-750/562

N/A

1000A

800A

PW9315-750/600
PW9315-750/675

N/A

1200A

1000A

16. Source protection for the AC input should be treated as if you were supplying a

750 kVA three-phase transformer, to allow for inrush current.

17. The input breaker (CB1) has a trip rating of 1200 amps AT and a standard

ampere interrupting capacity (AIC) of 65,000 in symmetrical RMS amps. An
optional 100,000 AIC breaker is available.

18. The input and bypass three-phase feeds should be symmetrical about ground,

due to the existence of voltage surge protection devices.

19. The line‐to‐line unbalanced output capability of the UPS is limited only by the

full load per phase current values for AC output to critical load shown in
Table E through Table G. The recommended line‐to‐line load unbalance is 50%
or less.

20. Output overcurrent protection and output disconnect switch are to be provided

by the user. Table L lists the maximum rating for continuous duty rated output
circuit breakers satisfying the criteria for both.