INSTALLATION REFERENCE

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201244 Rev E www.powerware.com

A-15

Table G. Input/Output Ratings and External Wiring Requirements (PW9315-750/600 and PW9315-750/675)

Basic Unit Rating

PW9315-750/600 at 0.8 Lagging pF Load
PW9315-750/675 at 0.9 Lagging pF Load

Units

Rating 50/60 Hz

kVA/kW

750/600

750/600

750/675

750/675

Input and Output Voltage

Volts

480

600

480

600

AC Input to UPS Rectifier (0.95 Min. pF)

(3) Phases, (1) Neutral, (1) Ground

A

Amps*

1141

913

1181

945

Minimum Conductor Size
Number per Phase
* Maximum amps includes full load current plus
battery recharge current

AWG or kcmil

(each)

700

(4)

500

(4)

700

(4)

500

(4)

AC Input to MBC (UPS Bypass)

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

B

Amps

902

722

902

722

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

400

(4)

500

(3)

400

(4)

500

(3)

DC Input from Battery to UPS

(1) Positive, (1) Negative

C

Vdc

Amps @ (2.0V/cell)

384

1645

384

1645

384

1850

384

1850

Minimum Conductor Size
Number per Pole

AWG or kcmil

(each)

600

(6)

600

(6)

700

(6)

700

(6)

AC Output to Optional SBM

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

E

Amps

902

722

902

722

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

400

(4)

500

(3)

400

(4)

500

(3)

AC Output to Critical Load

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

D

Amps

902

722

902

722

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

400

(4)

500

(3)

400

(4)

500

(3)

NOTE

Callout letters A, B, C, D, and E map to Figure A‐8.