INSTALLATION REFERENCE

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201244 Rev E www.powerware.com

A-16

9.

Terminals E1 through E12 are 2‐hole bus bar mountings for standard NEMA
2‐hole barrel lugs. See Table H for power cable terminations, Table I for conduit
requirements, and Table J for recommended installation parts and tools not
supplied by Eaton. Section A.4 shows the location of the power cable
terminals inside the UPS.

Table H. Powerware 9315 UPS (500–750 kVA) Cabinet Power Cable Terminations

Terminal Function

Terminal

Function

Size of Pressure Termination

Tightening Torque

Bolt Size

AC Input to UPS Rectifier
(CB1 Input)

E1

Phase A

4 - 2 bolt mounting

76 Nm (56 lb ft)

1/2”

E2

Phase B

4 - 2 bolt mounting

76 Nm (56 lb ft)

1/2”

E3

Phase C

4 - 2 bolt mounting

76 Nm (56 lb ft)

1/2”

AC Input to MBC (UPS Bypass)

E6

Phase A

4 - 2 bolt mounting

76 Nm (56 lb ft)

1/2”

E7

Phase B

4 - 2 bolt mounting

76 Nm (56 lb ft)

1/2”

E8

Phase C

4 - 2 bolt mounting

76 Nm (56 lb ft)

1/2”

AC Output from Inverter to MBC or
SBM

E9

Phase A

4 - 2 bolt mounting

76 Nm (56 lb ft)

1/2”

E10

Phase B

4 - 2 bolt mounting

76 Nm (56 lb ft)

1/2”

E11

Phase C

4 - 2 bolt mounting

76 Nm (56 lb ft)

1/2”

E12

Neutral

4 - 2 bolt mounting

76 Nm (56 lb ft)

1/2”

AC Input to MBC from Inverter

E9

Phase A

4 - 1 bolt mounting

76 Nm (56 lb ft)

1/2”

E10

Phase B

4 - 1 bolt mounting

76 Nm (56 lb ft)

1/2”

E11

Phase C

4 - 1 bolt mounting

76 Nm (56 lb ft)

1/2”

E12

Neutral

4 - 1 bolt mounting

76 Nm (56 lb ft)

1/2”

AC Output to Critical Load from MBC

E9

Phase A

12 - 2 bolt mounting

76 Nm (56 lb ft)

1/2”

E10

Phase B

4 - 2 bolt mounting

76 Nm (56 lb ft)

1/2”

E11

Phase C

4 - 2 bolt mounting

76 Nm (56 lb ft)

1/2”

DC Input from Battery to UPS

E4

Positive

6 - 2 bolt mounting

76 Nm (56 lb ft)

1/2”

E5

Negative

6 - 2 bolt mounting

76 Nm (56 lb ft)

1/2”

DC Link Output from Rectifier to
Inverter

(+)

DC Link (+)

4 - 1 bolt mounting

13 Nm (9.6 lb ft)

Supplied

(–)

DC Link (–)

4 - 1 bolt mounting

13 Nm (9.6 lb ft)

Supplied

DC Link Input to Inverter from
Rectifier

Inverter (+)

DC Link (+)

6 - 1 bolt mounting

13 Nm (9.6 lb ft)

Supplied

Inverter (–)

DC Link (–)

6 - 1 bolt mounting

13 Nm (9.6 lb ft)

Supplied

Neutral, Output

E12

Neutral

12 - 2 bolt mounting

76 Nm (56 lb ft)

1/2”

Customer Ground

Ground

Ground

8 - 2 bolt mounting

76 Nm (56 lb ft)

1/2”

NOTE Customer ground, size 2/0, can be run in any conduit listed in Table I on page A-17.