COMMUNICATION

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201244 Rev E www.powerware.com

12-9

12.5

System Configuration Mode

The System Configuration mode allows you to modify special functions in your UPS.
These functions include programming of building alarms, customizing building alarm
messages, adjusting the nominal output voltage, and scheduling battery tests. The
menus provided and their function are described in the following sections.

12.5.1

System Configuration Mode Main Menu

When the System Configuration mode is selected with a terminal attached, you are
prompted to enter the password for this mode:

Please Enter Password:

The default password is POWER1. You may modify this password using the change
password function in the following menu. When the valid password is entered, the
Main menu is displayed:

Program Mode Main Menu

1. Program Building Alarms

2. Program Unit Name

3. Adjust Output Voltage

4. Change Password

5. Battery Test Setup

6. Modify Low Battery Time

7. Exit Program Mode

Enter Selection:

12.5.2

Program Building Alarms

This menu provides access to all the functions available in the System Configuration
mode. If 1 is entered at the prompt, you can program the building alarm functions:

Program Building Alarms

1. Enable/Disable Default Functions

2. Customize Alarm Messages

3. Return to Main Menu

Enter Selection:

12.5.3

Enable/Disable Default Functions

From this menu you may either enable the building alarms for general functions or
special functions, such as On Generator, Go To Bypass, and Go To UPS. You may
also customize the alarm messages from this menu. When 1 is selected, the
following menu is displayed:

Enable/Disable Default Functions

1. Enable/Disable Go To Bypass

2. Enable/Disable Go To UPS

3. Enable/Disable On Generator

4. Enable/Disable Building Alarm

5. Return to Program Building Alarms Menu

Enter Selection: