Powerware 9315 User Manual

Page 127

Advertising
background image

INSTALLATION REFERENCE

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201244 Rev E www.powerware.com

A-17

10. Per NEC, Article 300‐20(a), all three-phase conductors must be run in the same

conduit. If a neutral and/or ground is used, it must be run in the same conduit
as the phase conductors.

11. Conduit is sized to accommodate one neutral conductor the same size as the

phase conductor (if applicable) and one 2/0 ground conductor.

12. Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW,

RHW‐2, TW, THW, THHW, THW‐2.

Table I. Power Cable Conduit Requirements

UPS Model

Voltage

Terminal

Number of Wires

in Conduit

Minimum Conduit

Trade Size

Number of

Conduits

PW9315-750/600
PW9315-750/675

600

AC Input to UPS (A, B, C, Ground)

5

3.5”

3

AC Input to MBC (A, B, C, Ground)

4

3”

3

Output (A, B, C, Neutral, Ground)

4

3”

3

384

Battery

(Positive, Negative, Ground)

4

4”

3

PW9315-750/600
PW9315-750/675

480

AC Input to UPS (A, B, C, Ground)

5

4”

3

AC Input to MBC (A, B, C, Ground)

6

3.5”

3

Output (A, B, C, Neutral, Ground)

6

3.5”

3

384

Battery

(Positive, Negative, Ground)

4

4”

3

PW9315-750/500
PW9315-750/562

600

AC Input to UPS (A, B, C, Ground)

5

3”

3

AC Input to MBC (A, B, C, Ground)

5

3”

3

Output (A, B, C, Neutral, Ground)

5

3”

3

384

Battery

(Positive, Negative, Ground)

4

3.5”

3

PW9315-750/500
PW9315-750/562

480

AC Input to UPS (A, B, C, Ground)

5

3.5”

3

AC Input to MBC (A, B, C, Ground)

4

3”

3

Output (A, B, C, Neutral, Ground)

4

3”

3

384

Battery

(Positive, Negative, Ground)

4

3.5”

3

PW9315-625/500
PW9315-625/562

400

AC Input to UPS (A, B, C, Ground)

4

3.5”

4

AC Input to MBC (A, B, C, Ground)

5

3.5”

3

Output (A, B, C, Neutral, Ground)

5

3.5”

3

384

Battery

(Positive, Negative, Ground)

5

4”

2

PW9315-625/400
PW9315-625/450

400

AC Input to UPS (A, B, C, Ground)

5

3”

3

AC Input to MBC (A, B, C, Ground)

5

3”

3

Output (A, B, C, Neutral, Ground)

5

3”

3

384

Battery

(Positive, Negative, Ground)

5

3.5”

2

Advertising