INSTALLATION REFERENCE

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201244 Rev E www.powerware.com

A-18

Table J. Recommended Installation Parts and Tool (Not Supplied by Eaton)

Part

Size

Quantity

Manufacturer

Part Number

Notes

Long Barrel 2 Hole Lug

500 MCM

As required

Thomas & Betts

54876BE

Color Code: Brown

Die Code: 87

Bolt, Grade 5

1/2”

2”

1

N/A

N/A

Quantity per lug hole

Flat Washer

1/2”

1

N/A

N/A

Lock Washer

1/2”

1

N/A

N/A

Nut

1/2”

1

N/A

N/A

Manual Hydraulic Crimp Tool

14 Ton

1

Thomas & Betts

TBM14M

Die Set

N/A

1

Thomas & Betts

15506

13. Standard breakers used in the UPS are rated for 65 KAIC, with optional

breakers rated for 100 KAIC. To prevent cable whipping, secure cables as
shown in Figure A‐10. Wrap line cables together with nominal 9.5 mm (3/8”)
nylon rope or rope having a minimum tensile strength of 8896 N (2000
pounds). Wrap line cables at 152 mm (6”) and 1305 mm (2”) from the line
terminals with 5 wraps. Wrap each additional 152.4 mm (6”) interval with
5 wraps or 25.4 mm (1”) intervals with 1 wrap.

152 MM [6 INCHES]

NYLON ROPE -9 MM [3/8
INCH] DIAMETER.
MINIMUM OF FIVE WRAPS.

Figure A‐10. Securing Cables