INSTALLATION REFERENCE

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201244 Rev E www.powerware.com

A-9

A.2

UPS System Oneline Configurations

NOTE A bypass neutral feeder must be supplied when the output neutral is used. If no bypass neutral
feeder is supplied, the output neutral of the UPS is to be connected to chassis ground.

NOTE Output voltage must match bypass input voltage.

Table D. Powerware 9315 UPS System Oneline Configurations

Oneline Drawing

Powerware Model

Vin / Vout

System Type

Figure A‐8

PW9315-625/500

400/400

Single Module – Reverse Transfer

Single or Dual Feed

PW9315-625/625

PW9315-750/625

480/480

PW9315-750/750

PW9315-750/625

600/600

PW9315-750/750

Figure A‐9

PW9315-625/500

400/400

Multi-Module – Parallel

Capacity/Redundant

PW9315-625/625

PW9315-750/625

480/480

PW9315-750/750

PW9315-750/625

600/600

PW9315-750/750