INTRODUCTION

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201244 Rev E www.powerware.com

1-4

1.2.6

Monitoring and Communication

The following monitoring and communication options are available:

S

Remote Monitor Panel (RMP) – An optional RMP contains backlit status indicators and
a local horn, allowing you to monitor the UPS operational status and alarm
condition from virtually any location within your facility. This option is described
further in Chapter 10, “Using Features and Options.”

S

Relay Interface Module (RIM) – An optional RIM uses relay contact closures to
indicate the UPS operating status and alarm condition. The module uses a serial
interface line and may support up to eight critical loads. This option is described
further in Chapter 10, “Using Features and Options.”

S

Supervisory Contact Module (SCM) – An optional SCM establishes an interface
between the Parallel Capacity/Redundant system manufacturer's equipment and
the customer's monitor. This interface allows the customer to monitor operational
status of the Parallel Capacity/Redundant system equipment. This option is
described further in Chapter 10, “Using Features and Options.”

S

X-Slot Cards – Optional X-Slot cards support several protocols, such as SNMP,
AS/400

®

, and Modbus

®

. See Chapter 12, “Communication,” for additional

information.

S

eNotify Remote Monitoring and Diagnostic Service – An optional service that provides
7x24 remote monitoring of 43 alarms, temperature/humidity and battery charge
information, daily heartbeat check, and monthly report. The eNotify service also
provides customer notification of significant alarms, remote diagnostics, and
dispatch of technicians. A ConnectUPS -X Web/SNMP Card is required in the
X-Slot communication bay. An optional Powerware Environmental Monitoring
Probe (EMP) is required for temperature/humidity monitoring. See Chapter 12,
“Communication,” for additional information.

S

Modem – An optional modem is available for use with the Remote Notification
feature described in Chapter 12, “Communication.” Refer to the modem
manufacturer's manual for modem operating instructions.

1.3

Basic System Configurations

The following basic UPS system configurations are possible:

S

Single module UPS and one battery string

S

Multi‐module (parallel for capacity/redundancy) UPS system consisting of two or
more UPS modules, with one battery string for each module, and a Powerware
Hot Sync

®

Capacity module

S

Multi‐module (parallel for capacity/redundancy) UPS system consisting of two or
more UPS modules, with one common battery string, and a Powerware Hot Sync

®

Capacity module

You can enhance the UPS system configuration by adding optional accessories, such
as an RMP, RIM, SCM, or remote emergency power-off (REPO) control.