6 unit statistics screen, Unit statistics screen, Figure 8‐9. unit statistics screen – Powerware 9315 User Manual

Page 66

Advertising
background image

USING THE CONTROL PANEL

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201244 Rev E www.powerware.com

8-10

8.5.6

Unit Statistics Screen

Select Unit from the Statistics menu to display a listing of statistics about UPS
operation.

Figure 8‐9 shows the Unit Statistics screen.

Uninterruptible Power System

UPS System Normal

Events

Statistics

Graphics

Setup

Meters

Statistics

Unit

Start Date: 04 MAY 1999

Number of Incidents:

On Battery < 1 Min.

On Battery 1-4 Min.
On Battery > 4 Min.
Full Batt. Discharge
Building Alarm 1
Building Alarm 2
Building Alarm 3
Building Alarm 4
Building Alarm 5
Building Alarm 6

UPS
Bypass
Battery
Generator
Logic

Availability
UPS
Bypass

0
1
0
0
2
2
3
2
3
3

0
0
0
0

11

9
8
5
8
9

0.99
0.81

48.5

Minutes

Battery

Month Total

DAYS HR MN

Time On:

0035 20 59
0000 00 30

0000 00 02
0000 00 00

0035 21 30

ALARM: NONE
NOTICES: NONE

4 MAY 1999 09:25:42

Figure 8‐9. Unit Statistics Screen

The left column shows the number of UPS incidents for the current month and since
the start date shown at the top of the information area. The top right column shows
the time that the UPS was on bypass, battery, or generator, and the amount of time
the UPS logic has been functioning since the start date. The lower right column
shows the percent of availability of the UPS and the bypass source.