- 63 -

Protection

Overload

error

Alarm

Code No.

1 6

C o u n t e r m e a s u r e s

Check on waveform graphic screen of
P A N A T E R M

w h e t h e r t h e t o r q u e

( c u r r e n t w a v e ) i s s u r g i n g o r n o t .
Check the overload alarm message
and load factor using PANATERM

.

1) Increase the capacity of the amplifier and

motor. Lengthen the ramp time of accel-
eration/deceleration. Re-duce the motor
load.

2) Readjust the gains.

Adjust setting of the rotary switch.

3) Correct the motor wiring per the wiring

diagrams. Replace cables.

4) Free the machine of any tangle. Reduce

the motor load.

5) Measure the voltage at the brake wiring

connections. Turn off the brake.

6) Correct the motor and encoder wiring to

eliminate the mismatching.

Check regenerative discharge resistor load
factor on monitor screen of PANATERM

.

The amplifier should not be used with con-
tinuous regenerative braking.
1) Check the operation pattern (using the

velocity monitor). Check the load rate of
the regenerative resistor and the over-
regeneration alarm on display.Increase the
capacity of the amplifier and motor.
I n c r e a s e t h e d e c e l e r a t i o n t i m e .
U s e a n e x t e r n a l r e g e n e r a t i v e
resistor.

2) Check the operation pattern (using the ve-

locity monitor). Check the load rate of the re-
generative resistor and the over-regeneration
alarm on display. Increase the capacity of the
amplifier and motor. Increase the decelera-
tion time. Reduce the motor rpm. Use an ex-
ternal regenerative re sistor.

3) Set "2" on Pr6C.

Important

information

C a u s e

Overload protection is activated via
the specified time limiting operation
when the integration of a torque com-
mand exceeds the specified overload
level.

1) Caused by a long operation with a torque

that exceeds the specified torque limit.

2) Vibration or hunting due to incor- rect

gains. Cause vibration and/or abnormal
sound.
A d j u s t m e n t o f i n e r t i a r a t i o , s e t
value of Pr20, is required.

3) Motor wires connected wrong or broken

4) The machine is hit against a heavy thing,

or suddenly becomes heavy in operation.
The machine is entangled.

5) The electromagnetic brake is ON.

6) In a system of multiple amplifiers, some

motors are wired incorrectly to other axis.

The regenerative energy is larger than the
capacity of the regenerative discharge re-
sistor.

1) When the load inertia is too large, he

converter voltage increases due to the
large energy regenerated during decel-
eration, and increases more due to the
shortage energy consumption by the re-
generative discharge resistor.

2) When the velocity of the motor is too high,

the regenerative energy cannot be con-
sumed within the specified deceleration
time.

3) Operation of external resistor is limited

to 10% duty.

1 8

Regenerative

discharge

< N o t e s >
When setting Pr6C to "2", don't fail to install external protection such as thermal fuse.
Otherwise, regenerative discharge resistor is not protected any more to cause possible
abnormal heat generation, resulting in burning of the motor.