To place the 4100U-S1 into operation, perform the following steps:

STEP 1

Ensure that the Mains Switch is OFF.


STEP 2

Ensure that 240 VAC is connected to the panel from the mains distribution

switchboard.


STEP 3

Ensure that the Lithium battery is fitted to battery holder on the CPU card,

and link P3 is fitted to the BAT ON position.


Turn the Mains Switch ON.


STEP 4

Check that the green "MAINS ON" LED indicator is on.

The Controller performs tests on its memory, electronics, and the LCD.


STEP 5

Check that the buzzer sounds and the LCD display “CPU Serial Number”.


STEP 6

Check that the LCD has good visibility. Adjust the LCD Contrast control

on the inside of the keyboard door, if necessary.


STEP 7

Install and connect the batteries.

Take care not to short the battery leads or connect in reverse polarity when

connecting.

STEP 8

Press the Lamp Test key on the control panel and check that all LEDs turn

on, and the LCD shows all black squares.


STEP 9

Clear any faults one at a time.

A full commissioning test must be carried out as per the requirements of AS 1670.1.
Refer to the appendix in this manual for detail on checking wiring, and earth fault
detection. Refer to the 4100U-S1 Operator’s Manual LT0395 for detail of the walk test
that may be used for verifying correct detector operation.


Power Up & Placing into Operation