Connector

block mounted

on bracket

FB

COM

NO

FB

T-GEN 50

10 k ohm

resistor

LINE -

LINE +

EARTH

DC

I

N

PU

T

+24V

+24V

0V

0V

ALM-

A/I/E-

SIG

DEF-

F

AUL

T RE

L

AY

OU

T

P

U

T

COM

NC

NO

To AUX

POWER

4100-3003

Relay

Module

Mains rated cable for

100V speaker wiring

Auto 150 (1.0 mm

2

)

or heavier

Figure 5-4. Relay Module Connection to a T-Gen 50


A T-GEN 50 can be operated and supervised using a 4100-3003 relay module. The relay
module is used to control the ALM- input to the T-GEN 50 and to monitor the state of its
Fault relay. The T-GEN 50 is configured to supervise the ALM- wiring from the relay
module and the 100V wiring to the loudspeakers.

Figure 5.4 shows the wiring between the T-GEN 50 and the relay module. The detail of
the 24V supply is not shown, but the T-GEN 50 0V MUST be common with the 4100U
0V (this will always be the case when using the AUX POWER supply, as described
earlier).