T-gen 50 settings for nac operation, T-gen 50 settings for nac operation -12 – Tyco 4100U-S1 User Manual

Page 80

Advertising
background image

5-12




These switch and link settings should be used. These apply to T-GEN 50 software
version 1.7.

Alert to Evacuate

Change-Over Time

SW1

(T0)

SW2 (T1)

SW3

(T2)

Setting on T-GEN 50

OFF OFF OFF

0

sec

ON OFF OFF

30

sec

OFF ON OFF

1

min

ON ON OFF

1.5

min

OFF OFF ON

3

min

ON OFF ON

5

min

OFF ON ON

10

min

ON ON ON

Alert

Only


SW1 to SW3 settings have no effect on Slave T-GEN 50s.

SWITCH

Name

Setting on T-GEN 50

SW4 ALM

I/P

Supervision

OFF (Supervision disabled)

SW5

ALM I/P

OFF (Non-latching)

SW6 OFF

SW7

Evac Tone

OFF for AS 2220 tone
ON for ISO 8201 + Keywords

SW8

Evac Message

OFF for Evac Message 1 or Field
Recorded message,
ON for Evac Message 2 or Keywords
only in ISO 8201


Link

Name

Setting on T-GEN 50

1

BIAS

Can be FITTED if PA or Background

Music not required

2 MASTER

FITTED

3

REC EN

Fit to record message.

4

TEST

Fit for test tone during installation

5 SLAVE

NOT

FITTED

6

SLAVE / MASTER

MASTER

7 FAULT=

DEF-/RELAY

RELAY




Using T-Gen 50 with 4100U-S1,

Continued

T-Gen 50 Settings for
NAC Operation