Compatible detectors, idnet – Tyco 4100U-S1 User Manual

Page 126

Advertising
background image

F-4


The following lists the detectors approved for use with IDNet and shows current
rating and numbers allowed per loop.

Device Type

Operating

Current mA

Maximum

Number Allowed

Per Loop

Maximum

Number

Allowed Per

Line

4098-9714E

Analogue Photoelectric

Smoke Detector

0.5

(2 with LED

on)

250 40*

4098-9717E

Analogue Ionisation

Smoke Detector

0.5

(2 with LED

on)

250 40*

4098-9733E

Analogue Heat Type A &

B Detector

0.5

(2 with LED

on)

250 40*

4098-9754E

Analogue Multi

(Heat/Photo)

Detector

0.5

(2 with LED

on)

250 40*


* Maximum allowed by AS1670.1.

The 9714E, 9717E and 9733E detectors use a (4098-) 9789E addressable base
or 9794E addressable sounder base, or 9793 addressable isolator base. The
9754E uses a 9796E addressable base or 9795E sounder base.

The maximum specified loop/line resistance is 40

Ω.


The maximum number of LEDs switched on during Alarm on an IDNet loop is 20.



Compatible Detectors, IDNET