Some or all of these output functions could be implemented using addressable
devices or other relay modules instead, in which case the corresponding NAC output
could be reassigned to other uses. The new configuration would require full testing
of these functions to ensure compliance with AS 4428.1.

To connect the SPS to reverse-polarity, non-addressable notification appliances using
Class A wiring, read the following instructions and refer to the figure below.

1. Route wire from the “B+”, “B-”, outputs on TB2 of the SPS to the appropriate

inputs on a peripheral notification appliance. Use NAC1, NAC2, or NAC3 as
required.

2. Route wire from the first appliance to the next one. Repeat for each appliance.

3. Route wire from the last appliance to the A+ and A- inputs on the same NAC

circuit of TB1 of the SPS.

4. Repeat steps 1 through 3 for each NAC output you want to use.

5. Leave the 10 K, ½ W, brown/black/orange resistor (378-030) on each the “B+”

to “B-” terminals of each unused NAC. No external end-of-line resistor is
needed for circuits in use.

6. If the appliance/device to be used does not have an integral diode, a sufficiently

rated blocking diode must be fitted between the incoming +ve wire and the +ve
terminals of the device with cathode (stripe) to the device.

P1

3
2

1

B+ B- A+ A-

TYPICAL

APPLIANCE

RED

RED

RED

NAC1

B+ B- A+ A-

NAC1

B+ B- A+ A-

NAC1

LED1

LED2

LED3

TYPICAL

APPLIANCE

BLK

BLK

BLK

NAC2

NAC3

Figure 5-2. Class A (loop) NAC Wiring

Continued on next page

SPS NAC Field Wiring Guidelines,

Continued

Class A (loop) NAC
Wiring

0.75 mm

2

to 4 mm

2

Important: Conductors

must test free
of all grounds.

Leave the 378-030 EOL
Resistor (10 K Ohm, ½ W;
brown/black/orange) on
unused B+/B- terminals

Ferrite beads

required for EMC

compliance. Use

SX0005 or kit

4100-5129.

NAC1

NAC2

NAC3

Advertising