Sps specifications, Input/output/batteryspecifications, Sps specifications -2 – Tyco 4100U-S1 User Manual

Page 60: Input/output/batteryspecifications -2

Advertising
background image

4-2


The following table summarizes the specifications for the SPS.

Table 4-1. SPS Input and Output Specifications

AC Input Specifications

SPS in Basic 4100U-
S1 (4100-9848AU)

240 VAC + 6% -10% @ 50 Hz
2 A Maximum

DC Output Specifications

Voltage

Nominal 28VDC
Minimum: 19.5 VDC Maximum: 32 VDC
Ripple: 2 VDC p-p @ full load (9A)

Total Current (max)






24V Card

24V Aux


Each NAC (total A+B)

9A alarm load. Includes: NACs; +24V Card;
+24V Aux; SPS card including on-board IDNet.

5A non-alarm load. Includes the above
allowances, and allows for battery charging at
high rate.

2A max. See note.
2A max

3A max alarm load
2A max non-alarm load (when used as AUX
24V power).

SPS IDNet Output

30 V or 35 V (see note below)

Battery Charger Specifications

Input Voltage Range

21-33 VDC

Output Float Voltage

27.3 VDC

±200 mV @ 20°C, temperature

compensated at approximately -36mV/

°C

(0

° C to 50° C)

Supervision Voltages
(nominal at 20

°C)

Charger High

28.4Vdc

Charger Low

26.2Vdc

Battery Low

24.3Vdc

Battery Depleted

19.4Vdc

Output Current Limit

1.4 A (For 6.2 – 18 Ah battery)
3.3 A (Default; for 18-110 Ah battery)

Notes:

• AC power must be provided to the 4100U-S1 from a dedicated AC branch circuit.

The AC input is supervised wiring.

• The AC branch is terminated in the cabinet in the general power output (GPO)

mounted in the expansion bay. The SPS plugs into the GPO via a 3-pin plug and
mains lead.

• A mains fail fault is generated when the DC voltage drops below 20.3V (nominally at

mains voltage 204VAC).

Continued on next page

SPS Specifications

Input/Output/Battery
Specifications