The alarm relay card, Overview, Mounting (factory installed) – Tyco 4100U-S1 User Manual

Page 65: The alarm relay card -7, Overview -7, Mounting (factory installed) -7, Figure 4-1. the alarm relay card -7

Advertising
background image

4-7


The Alarm Relay Card mounts on, and is driven by, the SPS. It has 3 relays, each
providing one set of voltage-free contacts. It is fitted to the basic 4100U-S1 as standard.

The relays are able to be configured under custom control, but the default operation is for
system status, i.e. Fault (Trouble), Isolate (Supervisory), and Alarm, respectively. These
are commonly used to drive the Brigade signalling device (ASE or PPU/AIU). See the
next section for more details about Brigade Devices.

TROUBLE

SUPERVISORY

ALARM

F3

F2

F1

p
3

p
2

p
1

LD1

LD2

LD3

Fault

(Trouble)

Isolate

(Supervisory)

Alarm

10 Way FRC

connects to P7

on SPS

Energised Relay LEDs

Normally Closed/
Normally Open
Jumpers

3A, 5 x 15mm Fuses

TB1 Terminal Block

Figure 4-1. The Alarm Relay Card


The Alarm Relay Card mounts on the SPS adjacent to the largest relay K3. With the
power disconnected, fit the card using the three plastic stand-offs and one Torx screw
with plastic sleeve.

Connect P4 on the relay card to P7 on the SPS with the 10 way FRC provided.


The Alarm Relay Card

Overview

Mounting
(factory installed)