Class b (string) wiring, Class b (string) wiring -20, Figure 5-10. class b (string) wiring -20 – Tyco 4100U-S1 User Manual

Page 88: Sps idnet wiring, Continued

Advertising
background image

5-20


To connect addressable devices/detectors to the SPS IDNet using Class B wiring, read the
following instructions.

1. Under AS1670.1 Class B wiring is allowed only for a maximum of 40

addressable devices.

2. A ferrite bead is required on the SPS IDNet cable.

3. On TB1, jumper B+ to A+, and jumper B- to A-.

4. Route wire from the B+, B- terminals to the devices.

The illustration below shows Class B wiring.

B+ B- SHLD

IDNet

A+

P1

3
2

1

A-

IDNet LINES TO DEVICES

(CLASS B / STYLE 4)

Figure 5-10. Class B (string) Wiring


SPS IDNet Wiring,

Continued

Class B (string)
Wiring

Ferrite bead

required.