This appendix briefly summarises the programming that is required to comply with
AS4428.1.

It does not provide equations or detail of programming. Refer to LT0400 4100U-S1
Programming & Configuration Reference for descriptions of the AS 4428.1
programming. The separate 4100U Programming Manual tells how to use the PC-based
4100U Programmer.

The following is a list of functions that must be programmed under custom control.
Functionality must comply with AS4428.1, and be as described in the Operator’s Manual
LT0395.

• Individual zone alarm indication, flashing until isolated, steady when isolated.

• Common Zone Alarm indication, flashing when any zone in alarm is un-isolated,

steady when all zones in alarm are isolated.

• Individual zone isolate pushbutton and indication.

• Zone Alarm Test pushbutton and indication.

• Zone Fault Test pushbutton and indication.

• Warning System Isolate pushbutton and indication.

• External Bells Isolate pushbutton and indication.

• Ancillary Control Function and Isolate pushbutton and indication as required.

• Weekly 1 hour battery test.

• Fault indication after 8 hours of isolate.

The configuration templates for the 4100U-S1 all contain the necessary Custom Control
equations for these functions. These settings should not be altered except under advice
from Simplex.

• The US options for power supply and AVF are selected, not the Canadian ones.

• Features that do not comply with AS4428.1 must not be enabled, e.g. Alarm cut-out

times.

• Features that are statutory in AS4428.1 must not be pass-code protected, e.g. zone

isolate, zone test (Fault and Alarm).