Configuring the led/switch controller card, Mounting led/switch modules to the expansion bay, Configuring the led/switch controller card -19 – Tyco 4100U-S1 User Manual

Page 37: Figure 2-13. led/switch card mounting -19, Continued

Advertising
background image

2-19


If more than 32 zones are required, a second controller (4100-1289) will be required.

Note that an ME0456 fan control module counts as 8 zones when adding up the controller
requirements.

LED 1. This LED illuminates if communication loss between the controller and the CPU
occurs. It is independent of jumper P1 (which configures different communication loss
features).

The 64/64 LED/switch controller requires physical configuration, but the LED/Switch
modules do not. Switch controller configuration consists of setting jumper P1 and setting
the card address. In the 4100U-S1, the first display controller is address 3 and the second
has address 4. Card addressing is covered in Appendix A.

Refer to the figure below to mount the display cards to the front of the expansion bay.

Figure 2-13. LED/Switch Card Mounting

Continued on next page