Configuring the card, Overview, Setting the shield tie point – Tyco 4100U-S1 User Manual

Page 93: Setting the address, Configuring the card -5, Overview -5, Setting the shield tie point -5, Setting the address -5, Figure 6-3. dip switch sw1 -5

Advertising
background image

6-5


Configuring the card consists of selecting the shield tie point, and setting the card address.

If a shielded cable is used, connect the cable shield to the dedicated terminal on TB1 and
use jumper port (P1) to select where the shield will be tied.

• Position 1 - 2 connects the shield to 0 V.
• Position 2 - 3 connects the shield to Earth.

The card address is set on DIP switch SW1, which is a bank of eight switches (see figure
below). From left to right, these switches are designated as SW1-1 through SW1-8. The
function of these switches is as follows:

SW1-1. This switch sets the baud rate for the internal communications line

running between the card and the CPU. Set this switch to ON.

SW1-2 through SW1-8. These switches set the card’s address within the

4100U-S1. Refer to the table in Appendix A for a complete list of the switch
settings for all of the possible card addresses.


Note: You must set these switches to the value that was assigned to the card

by the 4100U Programmer.






1

8

7

6

5

4

3

2

Figure 6-3. DIP Switch SW1



Configuring the Card

Overview

Setting the Shield
Tie Point

Setting the Address

ON

OFF

Dip Switches SW1-2 through
SW1-8 set the Card Address.
Figure shows an Address of 3.

4100 Comms Data Rate.
Switch (SW1-1)
Must Be Set to ON