Page 85: Alarm relay card, Sps relay wiring -17, Overview -17, Aux 1 relay -17, Alarm relay card -17

Advertising
background image

5-17


The SPS has one programmable relay, Aux 1, with one set of voltage-free contacts (see
below).

The Alarm Relay 4100-6033 is fitted as standard to 4100U-S1. This has 3 relays, each
with one set of normally open (or normally closed) contacts available on a screw terminal
block (see Chapter 4).


• The relay must be configured in the Programmer.
• The relay circuit is rated to switch 2A resistive or 1A inductive at 30VAC or 32VDC.
• Relay contacts are Form C voltage-free contacts (but with a 40V transorb from

common to Earth). Do not switch voltages greater than this rating, or damage may
result.

• When power through the relay contacts is provided by the SPS Auxiliary Power

output, wiring is power-limited.

• The relay circuit is not supervised.

The three relays have default functions of Fault (trouble), Isolate (supervisory) and
Alarm, and are typically used for Brigade Signalling (refer to Chapter 4 for jumper
settings and other Brigade device information).

Continued on next page

SPS Relay Wiring

Overview

Aux 1 Relay

Alarm Relay Card