General field wiring guidelines, General guidelines, General field wiring guidelines -2 – Tyco 4100U-S1 User Manual

Page 70: General guidelines -2, Figure 5-1. the ferrite bead -2

Advertising
background image

5-2

• All field wires must be 0.75 mm

2

or greater cross section and comply with

AS1670.1 and the wiring code.

• Conductors must test free of all earth leakage.
• All wiring must be done using copper conductors only, unless noted otherwise.
• If shielded wire is used,

-

the metallic continuity of the shield must be maintained throughout the
entire cable length.

-

the entire length of the cable must have a resistance greater than 1 Megohm
to earth ground.

• Underground wiring must be free of all water.
• Wires that run in plenum should be in conduit.
• A system ground must be provided for earth detection and lightning protection

devices. This connection must comply with approved earth detection.

• Only system wiring should be run together in the same conduit.
• Use supplied ferrite beads with all SPS field wiring including the Aux 24V.

Loop wires twice through the supplied ferrite bead(s) as shown in Figure 5-1.
(Extra can be ordered as 4100-5129 – 3 beads).

Figure 5-1. The Ferrite Bead


Continued on next page

General Field Wiring Guidelines

General Guidelines

Wires go twice
through (1 turn)