5-19


To connect addressable devices/detectors to the SPS IDNet using Class A wiring, read the
following instructions.

1. Ferrite beads are required on the SPS IDNet cables (refer Figure 5.1).

2. Route wire from the B+, B- outputs on TB1 of the SPS to the appropriate inputs

on a peripheral IDNet device.

3. Route wire from the first IDNet device to the next one. Repeat for each device.

4. Route wire from the last IDNet device to the A+ and A- inputs on TB1 of the

SPS.

B+ B- SHLD

IDNet

A+

P1

3
2

1

A-

IDNet

DEVICE

IDNet

DEVICE

IDNet

DEVICE

IDNet LOOP

(CLASS A / STYLE G)

Figure 5-9. Class A (loop) Wiring

Continued on next page

SPS IDNet Wiring,

Continued

Class A (loop)