4-3

• The bulk supply (rated at 9A max) which feeds 24V Sig, 24V Card, 24V Aux also

supplies the SPS Card including the on board IDNet, and the battery charger. The
charger is disabled during alarms so as to make the 9A available on the other busses.
(See the following table for the SPS current).

• +24V Sig is used to supply the NACs. It can be made accessible for other use by

configuring a NAC as an auxiliary power output (normally energized).

• The battery circuit is checked every 29 seconds. The battery test is programmed via

custom control for a 1 hour test once per week.

• The battery is connected to the charger but is normally disconnected from the bulk

supply. During mains fail or the 1 hour battery test, the battery gets connected to the
bulk supply.

• The IDNet output is 30V in the normal condition so as to prolong battery standby.

When it is necessary to activate large numbers of output devices on IDNet
peripherals (such as piezo sounders), the output voltage is increased to 35V to
provide sufficient voltage at the end of line to activate piezo sounders. The higher
voltage state is an alarm condition for the purpose of standby battery calculation.

The following table summarizes battery standby capabilities for the SPS. Voltage
assumed is 24 V, which is the rated battery voltage for lead-acid type batteries.

Table 4-2. SPS Current Specifications

Standby Conditions

Current

• No alarms (NACs normal)

• IDNet LED ON, no IDNet devices connected

175 mA

Add to above for each additional set of 50 IDNet devices in
standby, with IDNet at 30 V

40 mA

Total current for fully loaded IDNet channel (250 devices) in
standby

375 mA

Alarm Conditions

Current

• 3 NACs ON

• IDNet LED ON, no IDNet devices connected

185 mA

Add to above for each set of 50 IDNet devices in alarm, 20
LEDs ON

80 mA

Add to above for each set of 50 IDNet devices in alarm, LEDs
OFF

50 mA

Total current for a fully loaded IDNet channel (250 devices) in
alarm, 20 LEDs ON

475 mA

Notes:
Additional standby conditions: Trouble relay activated, power trouble LED

on, IDNet LED on, battery charger off, auxiliary power load = 0 mA

Continued on next page