The power distribution interface (pdi), Mains outlet, The power distribution interface (pdi) -8 – Tyco 4100U-S1 User Manual

Page 26: Mains outlet -8, Continued

Advertising
background image

2-8


In the expansion bay, power and data are distributed via the power distribution interface
(PDI). The PDI is a wiring board with eight card slots, each of which can accommodate a
4-inch (102 mm) x 5-inch (127 mm) slave card. If 4100-style motherboards are used, they
must be mounted over the PDI using a kit of metal standoffs (part number 4100-KT0468).

4100 POWER DISTRIBUTION INTERFACE

ASSY 566-084

Figure 2-5. The Power Distribution Interface (PDI)


The rightmost 2” slot in the expansion bay is occupied by a mounting bracket holding a
single switched General Power Outlet. The fixed AC power wiring must be installed to
this GPO by a suitably qualified electrician.

IMPORTANT:
AC power must be provided to the 4100U-S1 from a dedicated branch
circuit.

The SPS plugs into this GPO, and can be switched off or unplugged for servicing.

Introduction to 4100U-S1 Cabinet,

Continued

The Power
Distribution
Interface (PDI)

Mains Outlet

POWER/COMMS

CONNECTORS

(P1-P3)

AUDIO INTERFACE

CONNECTORS

(P6, P7)

(Not used in 4100U-S1)

POWER SOURCE

JUMPERS

(P4, P5)