Installation mistakes in the standpipe – VEGA VEGAPULS 45 VBUS User Manual

Page 29

Advertising
background image

VEGAPULS 42, 44 and 45 – VBUS

29

Pipe antenna: The surge pipe open to the bottom
must have a ventilation or equalisation hole on top

Correct

Wrong

VEGAPULS 44 on the surge pipe: The sensor type
plate must be aligned with the rows of holes.

Type label

Correct

Wrong

Mounting and installation

Installation mistakes in the standpipe

Pipe antenna without ventilation hole

Pipe antenna systems must be provided with
a ventilation hole on the upper end of the
surge pipe. The lack of a hole will cause false
measurements.

Wrong polarisation direction

When measuring in a surge pipe, especially if
there are holes or slots for mixing in the tube,
it is important that the radar sensor is aligned
with the rows of holes.

The two rows of holes (displaced by 180°) of
the measuring tube must be in one plane with
the polarisation direction of the radar signals.
The polarisation direction is always in the
same plane as the type label.