VEGA VEGAPULS 45 VBUS User Manual

Page 65

Advertising
background image

VEGAPULS 42, 44 and 45 – VBUS

65

Switching delays are adjusted under
"

Configure".

• Click to "

OK".

• If you want to save your settings, you have

to click in the window "

Switching output" to

"

Save".

The settings are permanently saved in the
signal conditioning instrument (or in the
processing system) - even in case of mains
failure.

• Qui the menu window "

Switching output"

with "

Quit".

Adjustment with the PC on the signal conditioning instrument

• Click "

Info" to show the function e.g. of the

switching window, if the switching condition
between 20 % and 60 % should be "On".

You want to have a function "

Protection

against dry running of pumps", where e.g. a
pump in a drop vessel starts emptying at
36 % filling and switches off at 8 %.

• Click to "

Info" to show the diagram of the

pump control.