Conditioning/scaling vegamet – VEGA VEGAPULS 45 VBUS User Manual

Page 72

Advertising
background image

72

VEGAPULS 42, 44 and 45 – VBUS

Lin.
curve

Linear

Integr
ation
time

0 s

Adjust
ment

Signal
condit
ioning

Scal
ing

Enter in the menu window "

0 % corresponds"

the value of the 0 % filling. In the example of
the adjustment with the PC and the adjust-
ment software VVO this would be 45 for
45 liters.

• Confirm with "

OK".

With the "—>" key you change to the 100 %
menu. Enter here the value of your parameter
corresponding to a 100 % filling. In the exam-
ple 1200 for 1200 liters.

• Confirm with "

OK".

If necessary, choose a decimal point. How-
ever, note that only max. 4 digits can be
displayed. In the menu "

prop. to" you choose

the parameter (mass, volume, distance…)
and in the menu "

Unit" the physical unit (kg, l,

ft

3

, gal, m

3

…).

Linearisation:

OK

100.0%

at

m (d)

XX.XXX

Fill the vessel e.g. to 10 % and enter 10 % in
the menu "

Min. adjust" with the "+" and "–"

keys. Then fill the vessel, e.g. to 80 % or
100 % and enter 80 % or 100 % in the menu
"

Max. adjust" with the "+" and "–" keys. If you

do not know the distance, you have to calcu-
late it by incremental filling.

The indication stops flashing
and the adjustment will be
saved.

You have entered the min. value.

(max. adjustment)

Enter the max. adjustment like the min. ad-
justment with "+", "–" or "OK" (example: 1.270
m).

4. Conditioning/Scaling VEGAMET

(see operating instructions VEGAMET)

Under the menu item "

Conditioning/Scaling"

you choose the product distance at 0 % and
at 100 % filling. Then you enter the parameter
and the physical unit as well as the decimal
point, e.g. distance.

Adjustment with MINICOM or VEGAMET

Signal
condit
ioning

Scal
ing

0 %
corres
ponds

XXXX

100 %
corres
ponds

XXXX

Deci-
mal
point

888.8

prop.
to

Mass

Unit

Kg

A linear correlation between the percentage
value of the product distance and percent-
age value of the filling volume is preadjusted.
With the menu "Lin. curve" you can choose
between linear, spherical tank and cylindrical
tank. The creation of one’s own linearisation
curve is only possible with the PC and the
adjustment program VVO.