4 electrical connection, 1 connection and connection cable – VEGA VEGAPULS 45 VBUS User Manual

Page 30

Advertising
background image

30

VEGAPULS 42, 44 and 45 – VBUS

Electrical connection

4 Electrical connection

4.1 Connection and connection

cable

Safety information

As a rule, do all connecting work in the com-
plete absence of line voltage. Always switch
off the power supply before you carry out
connecting work on the radar sensors. Pro-
tect yourself and the instruments.

Qualified personnel

Instruments which are not operated with
protective low voltage or DC voltage must
only be connected by qualified personnel.

Connection and grounding

A standard two or four-wire cable (sensors
with separate supply) with max. 2.5 mm

2

can

be used for connection. The earth conductor
terminal is galvanically connected with the
process fitting (thread or flange).

Ex protection

If an instrument is used in hazardous areas,
the respective regulations, conformity certifi-
cates and type approvals for systems in Ex
areas must be noted (e.g. DIN 0165).

Intrinsically safe circuits with more than one
active instrument (instrument delivering elec-
trical energy) are not allowed. Please note the
special installation regulations (DIN 0165).

Note!

In Ex applications, grounding on both ends is
not allowed due to potential transfer. If an
instrument is used in hazardous areas, the
respective regulations, conformity certificates
and type approvals for systems in Ex areas
must be noted (e.g. DIN 0165).

Note the approval documents and the in-
cluded safety data sheet attached to the Ex
sensors.

Connection cable

Please note that the connection cables are
specified for the expected operating conditions
in your systems. The cable must have an outer
diameter of 5 … 9 mm (1/2 to 1/3 inch). Other-
wise the seal effect of the cable entry will not be
ensured.

Cables for intrinsically safe circuits must be
marked blue and must not be used for other
circuits.