VEGAPULS 42, 44 and 45 – VBUS

Adjustment with MINICOM or VEGAMET

Adjustment steps

In the following, you will see the menu
schematic of the adjustment module
MINICOM. The menu schematic of the
VEGAMET signal conditioning instrument is
shown in the operating instructions of the
signal conditioning instrument. Set up the
sensor in the numbered sequence. The
respective numbers are stated in the menu
schematics. Numbers 1 … 4 and 11 you will
find in the menu schematic of the VEGAMET
signal conditioning instrument. Numbers
5 … 10 you will find in the following MINICOM
menu schematic. These numbers can be
adjusted with the MINICOM and with VEGA-
MET.

1.

Configuration of the measurement loop;
as a rule, already preconfigured (see
operating instructions VEGAMET).

2.

Configuration of the input; as a rule, al-
ready preconfigured (see operating
instructions VEGAMET).

3.

Min/Max. adjustment (see operating
instructions VEGAMET).

4.

Conditioning/Scaling VEGAMET (see
operating instructions VEGAMET).

5.

Measurement in a standpipe.

6.

Operating range.

7.

Meas. conditions.

8.

False echo memory (only required when
errors occur during operation).

9.

Indication of the useful and noise level

10. Conditioning/Scaling of the sensor dis-

play .

11. Outputs (see operating instructions

VEGAMET).

Short explanations to the setup steps 1 … 11
follow.

1. Configuration of the measurement
loop

(see operating instructions VEGAMET)

First of all, you have to inform the signal con-
ditioning instrument which application (level,
distance, flow, …) you have and which sen-
sor (radar, ultrasonic, …) is connected.
Choose under mode "Standard" and under
option "No option".

2. Configuration of the input

(see operating instructions VEGAMET)

First of all, you have to inform the signal con-
ditioning instrument (only VEGAMET 515V)
which input (input 1 or 2) the sensor is
connected to.

3. Adjustment

(see operating instructions VEGAMET)

Under the menu item "

Adjustment" you inform

the sensor which measuring range it should
operate with.

You can carry out the adjustment without and
with medium. Generally, you will carry out the
adjustment without medium, as you can then
adjust without a filling cycle.

Max.

Min.

100 % (1.270 m) correspond
to 1200 liters

Span (4.58 m)

0 % (5.850 m) corresponds
to 45 liters