VEGAPULS 42, 44 and 45 – VBUS

85

Technical data

Ambient conditions

Vessel pressure

-1 … 16 bar (-100 … 1600 kPa)
-1 … 40 bar (-100 … 4000 kPa)

Ambient temperature on the housing

-30 °C … +80 °C

Process temperature (flange temp.)

-20 °C … +150 °C (option -40 °C … +150 °C)

Storage and transport temperature

-60 °C … +80 °C

Protection

IP 66 and IP 67

Protection class

II

Overvoltage category

III

Ex technical data

Comprehensive data in the attached approval documents (yellow binder)
Intrinsically safe version

- classification ia

intrinsically safe in conjunction with a separator
or safety barrier

- classification mark

II 2G EEx ia II T6

- Ex approved

Zone 1 (ATEX)
Zone 1 (CENELEC, PTB, IEC)

or

- classification mark

II 1G EEx ia IIC T6

- Ex approved

Zone 0, Zone 1 (ATEX)
Zone 0, Zone 1 (CENELEC, PTB, IEC)

Permissible ambient temperature
on the housing

- T6

-40 °C … +55 °C

- T5

-40 °C … +70 °C

- T4, T3

-40 °C … +85 °C

- T2, T1

-40 °C … +70 °C

Permissible ambient temperature on the
antenna system if used in Ex areas

- T6

-40 °C … +85 °C

- T5

-40 °C … +100 °C

- T4

-40 °C … +135 °C

- T3

-40 °C … +150 °C

1)

Similar to DIN 16 086, reference conditions acc. to IEC 770, e.g.
temperature 15 °C … 35 °C; humidity 45 % … 75 %; air pressure 860 mbar … 1060 mbar

2)

The adjustment time (also called actuating time, response time or adjustment period) is the time required by
the sensor to output the correct level (with max. 10% deviation) after a sudden level change.

3)

Average emitted power (electromagnetic energy) per cm² received on an object directly in front of the
antenna. The received emitted power depends on the antenna version and the distance.