VEGA VEGAPULS 45 VBUS User Manual

Page 55

Advertising
background image

VEGAPULS 42, 44 and 45 – VBUS

55

Adjustment with the PC on the signal conditioning instrument

False echo storage

With the menu item "

False echo storage" in

the menu "

Sensor optimisation" you can au-

thorise the sensor to save false echoes. The
sensor electronics then saves the false ech-
oes in an internal database and assigns them
a lower level of importance than the useful
echo.

• Click in the menu window to "

Sensor

optimisation" to the menu item

"False echo

storage".

• Now click in the opening menu window

"

False echo storage" to

"Learn false ech-

oes". A small window opens.

• Enter here the verified product distance

and click to

"Create new".

You hereby authorise the sensor to mark all
echoes before the product echo as false
echoes. This prevents the sensor from erro-
neously detecting a false echo as level echo.

• Click to

"Show echo curve".

The curve and the false echo marking are
shown.

• Quit the menu with

"Quit".

You are again in the menu window "

Sensor

optimisation".

With the menu item "

Reset" you reset all op-

tions in the menu "

Sensor optimisation" to

default.

• Quit the menu window "

Sensor optimisation"

with

"Quit".