VEGA VEGAPULS 45 VBUS User Manual

Page 31

Advertising
background image

VEGAPULS 42, 44 and 45 – VBUS

31

Electrical connection

Earthing on both ends (on the signal
conditioning instrument via the potential
separation capacitor)

Earthing on the sensor end

Screening

magnetic

low-frequency

high-frequency

ground currents

fields

electrical

electrical

and superimposed

fields

fields

potential currents

none

one side

++

two sides

+

+

++

++

++ good protection against electromagnetic pollution
+

protection against electromagnetic pollution

no protection against electromagnetic pollution

c

Note:

λ

(Lambda) =– – –

f

Example: Interfering frequency approx. 100 kHz

l > ––

λ

7

l < ––

λ

7

l cable length
c light velocity (300000 km/s)
f interfering frequency

λ

wavelength

This means that interference can be avoided by earthing on both ends (better on one end) in
case of an interfering frequency of 100 kHz up to a cable length of approx. 4000 m.

Screening of the sensor cable

Very often, the "electromagnetic pollution"
caused by electronic actuators, energy
cables and transmitting stations is so
considerable that the sensor cable must be
screened.

We recommend the use of screening to avoid
future interferences. However, you must
make sure that no ground equalisation

currents flow through the cable screening.
Ground equalisation currents can be avoided
by ground potential equalisation systems.
When earthing on both ends, it is possible to
connect the cable shield on one earth side
(e.g. in the switching cabinet) via a capacitor
(e.g. 10 nF; 1500 V) to the earth potential.
Use a very low-resistance earth connection
(foundation, plate or mains earth).

m

s

1

c

1

3 • 10

9

l <

– •

– =

– • –––––––––

= 4285 m

7

f

7

100 • 10

3

1

s

e.g. 10 nF,
1500 V AC

VEGAMET

515V

VEGAMET

515V

Advertising