VEGAPULS 42, 44 and 45 – VBUS

• Choose under "

Sensor no." "

A" and under

"

Parameter"

"Scaled" and click to "Save".

• Enter the meas. distance in m which you

have set in the Min/Max-adjustment and
the litre values corresponding to the min.
and max. value.

• Click to

"Save".

• Click in the window

"Sensor-Display" to

"Quit" .

• Click in the window "

Display of measured

value" to

"Quit".

You are again in the menu window "

Outputs".

• Click in the menu window "

Outputs" to

"

Quit".

• Click in the menu window "

Instrument data

parameter adjustment" to "

Quit".

You are again in the main menu window.

Show measured value

• Click in the main menu window to the menu

"

Display/Display of measured value" and

choose the measurement loop (in the
example, only one is available).

Adjustment with the PC on the signal conditioning instrument

Sensor-Display

• In the menu window "

Outputs" you click to

"

Display of measured value" and choose

"

Sensor-Display".

• Choose in the menu window "

Sensor Dis-

play" "Scaled", "

Volume", if you want to have

the values displayed, e.g. in litres. In the
example, a level of 45 … 1200 liters would
have been displayed.