VEGAPULS 42, 44 and 45 – VBUS

Adjustment with the PC on the signal conditioning instrument

You are then in the initial menu window "

In-

strument data parameter adjustment".

• Click in the menu window "

Instrument data

parameter adjustment" to "

Quit".

You are again in the main menu window.

Parameter adjustment 2

Linearisation

The correlation between level and filling vol-
ume is defined by the so-called linearisation
curves. If, in your vessel, there is a correla-
tion other than linear between level ("

Percent-

age value" of the level) and the filling volume
(linearised value of the filling volume), choose
in the menu window "

Conditioning" the menu

item "

Instrument data/Parameter adjustment/

Conditioning".

• Click in the menu window "

Conditioning" to

the menu item

"Linearisation".

The menu window "

Linearisation" opens, in

which a linear correlation between percent-
age value of the level and the percentage
value of the filling volume is preset. Beside
the two programmed linearisation curves
"

Horizontal cylindrical tank", and "Spherical

tank" you can also enter "user programmable
curves". Linear means there is a linear corre-
lation between level and volume.

User programmable linearisation curves

• Click to

"User programmable curve" to

enter your own vessel geometry or a user
programmable filling curve.

• Click to "

Edit".