VEGAPULS 42, 44 and 45 – VBUS

Visualised creation of a vessel linearisation curve

The adjustment program recognises the sensor type

1.3 Adjustment

Each measuring situation is unique. For that
reason, every radar sensor needs some
basic information on the application and the
environment, e.g. which level means "empty"
and which level "full". Beside this "empty and
full adjustment", many other settings and
adjustments are possible with VEGAPULS
radar sensors.

Adjustment and parameter setting of the
radar sensors is done with
- the PC and the adjustment program VVO
- the detachable adjustment module

MINICOM

- the VEGAMET signal conditioning instru-

ment

Adjustment with the PC

Setup and adjustment of the radar sensors is
generally done on the PC with the adjustment
program VEGA Visual Operating (VVO)
under Windows

®

.

By means of pictures,

graphics and process visualisation, the pro-
gram leads you quickly through adjustment
and parameterisation.

Product description

1.2 Application features

Applications

• Level measurement of all liquids.
• Measurement also in vacuum.
• All slightly conductive substances and all

substances with a dielectric constant > 2.0
can be measured.

• Measuring range 0 … 10 m (type 42).

Measuring range 0 … 20 m (type 44).
Measuring range 0 … 4 m (type 45).

Two-wire technology

• Power supply and output signal on one

two-wire cable (loop powered).

• VBUS output signal (VEGA-Bus).

Rugged and wear-free

• Non-contact.
• High resistance materials.

Exact and reliable

• Accuracy 0.05 %.
• Resolution 1 mm.
• Unaffected by noise, steam, dust, gas

compositions and inert gas stratification.

• Unaffected by varying density and tem-

perature of the medium.

• Measurements of pressures up to 40 bar

and temperatures up to 150 °C.

Communicative

• Integrated display of measured values.
• Optional display separate from the sensor.
• Adjustment with detachable adjustment

module which can be plugged into the
sensor or into the external display.

• Adjustment with signal conditioning instru-

ment.

• Adjustment with PC.

Approvals

• CENELEC, ATEX, PTB, FM, CSA, ABS,

LRS, GL, LR, FCC, RINA.