6 ex-technical data, 7 approvals, Whg-approval – VEGA VEGAMET 514… D User Manual

Page 11: Ex-approval, Product description

Advertising
background image

VEGAMET 514… D

11

1.6 Ex-technical data

Power supply

Operating voltage

U

nenn

corresponds to the not-Ex-version

Limit voltage

U

nenn

= 250 V AC or 125 V DC

Measuring data input (intrinsically safe circuit)

Classification

[EEx ia] IIC, [EEx ia] IIB, [EEx ib] IIC or [EEx ib] IIB

Max. values
- Voltage

U

O

= 20 V

- Current

I

O

= 128 mA

- Power

P

O

= 640 mW

Characteristics

linear

Effective inner inductance L

i

unimportant

Effective inner capacitance C

i

unimportant

EEx ia IIC

EEx ia IIB

EEx ib IIC

EEx ib IIB

Max. permissible outer inductance L

O

(mH)

0,5 1

1,5

2

2

9

Max. permissible out capacitance C

O

(nF)

97

78

68

486

200

1000

The intrinsically safe circuits are reliably separated from the not-intrinsically safe circuits up to a peak
value of the nominal voltage of 375 V.
The max. voltage on the not-intrinsically safe circuits must not exceed 250 V

eff

in case of failure.

1.7 Approvals

VEGAMET are available with the following approvals:
- Explosions protection: appropriate operating instrument with intrinsically safe(s)
- Overfill protection to WHG and VbF applied

Observe with these applications the appropriate legal documents (test certificates, type approvals and

conformity certificates). These are supplied with the respective instrument.

WHG-approval

Signal conditioning instrument as part of an overfill protection to WHG or VbF (applied).

Ex-approval

For hazardous areas, certificate to CENELEC defined in the conformity certificate

PTB-no. Ex-95.D.2161 X

.

Product description

Advertising