VEGA VEGAMET 514… D User Manual

Page 9

Advertising
background image

VEGAMET 514… D

9

Indicating element

Clear text indication

LC-display
- 4 line, 6 figures each
- background lightning

Analog indication

11 segments 0 % … 100 %
acc. to MST-enquiry

- %-value of level
- %-value of flow

LED in front plate

green on: operating voltage on
red: fault signal
yellow (per relay): relay switching condition

Operating elements

Front plate

6 keys for configuration and parameter adjustment

Ambient conditions

Permissible ambient temperature

-20

°

C … +60

°

C

Storage and transport temperature

-40

°

C … +80

°

C

Electrical connection

Multipoint connector component

acc. to DIN 41 612, series F, 36-pole (three row) d, b, z

(partly equipped)

Carrier BGT 596 (Ex)

connection to the respective module

Housing type 505

connection to screw terminals (max. 2,5 mm

2

)

Electrical protective measures

Protection
- unassembled

IP 00

- mounted into

carrier BGT 596
front side completely equipped: IP 40
upper and lower side: IP 20
wiring side: IP 00

- mounted into housing

- terminal housing

IP 20

- housing general

IP 30

Protection

II (in housing type 505 or type 506)

Overvoltage category

II

Electrical separating measures

Reliable separation acc. to VDE 0106,
part 1

between power supply, fail safe and level relay,
meas. data inputs and correction inputs

- limit voltage

250 V

- isolation resistance

2,3 kV

Galvanic separation

between relay outputs

- limit voltage

250 V

- isolation resistance

1,4 kV

Potential separation

between DISBUS, transistor outputs and correction

inputs
- limit voltage

50 V

- isolation resistance

0,5 kV

Common reference potential at

voltage/current outputs, correction inputs

Product description

>>

Advertising