Set-up, parameter adjustment

Adjustment

- Application

Flow measurement

- Sensor

ultrasonic sensors
radar sensors

Parameter adjustment MST1, adjustment

–– with measured product

With this adjustment procedure %-values have to be
adjusted each for min. and max. which correspond

to the actual measured distances between sensor
and level/flow.

–– Min. adjustment at

0.0 %

Range 0 … 80 %

–– Max. adjustment at

100.0 %

Range 20 … 100 %

a

of 20 % must be observed between min. and

max.

–– without measured product

For this adjustment procedure two future distances
(sensor … level/flow) must be adjusted which

correspond to 0 % and 100 %.

–– Adjustment in

m (d)

etc. if necessary modify unit, the unit is displayed
acc. to the menu point "Adjustment in"

–– 0 % at

0.80 m(d)

0.80 and 1.40

–– 100 % at

1.40 m(d)

corresponds e.g. to adjustment distances in m

Parameter adjustment MST2, adjustment as described above

If you want to detect the level and the flow as parameter, it is recommended to carry out the adjustment for
MST1 and MST2 at the same time, i.e. immediately one of the other.

e.g. rectangular weir
h

max.

= 0,60 m

100 % ^ 0,80 m (d)

0 % ^ 1,40 m (d)