4.7.2

Flow measurement

General information

In the following section elementary information to dimensions in front of flumes, walls and sensor installation

positions is given.

Flume with meas. section (e.g. Khafagi-Venturi flume)

Fth meas. wall (e.g. rectangular weir)

Note

General
- h

max

is the max. damming or overflow height acc. to the meas. section or meas. wall.

- All other dimensions are nearly derived from h

max

(see above drawings)

Sensor mounting position
- Mount sensor on the inlet /upstream water side.
- Observe distance 3 - 4 x h

max

from sensor to the throat or meas. wall.

- Mount the ultrasonic and radar sensors centred to the flume and vertically to the flow medium.
- Consider with ultrasonic sensors the min. distance to hmax.

Meas. wall
- Dimension dependent on h

max

.

- Thickness on the meas. wall (horizontal part) k

3 mm.

- Swelling of the meas. wall with a transition of 45

°

(see above drawing).

- Distance from the opening of the meas. wall to downstream water

5 cm.

Top view

Lateral view

3 - 4 x h

max

Sensor

90

°

min. distance

of the sensor

h

max

Sensor

Inlet side

Outlet side

Sensor

90

°

Sensor

h

max

min. distance

of the sensor

3 - 4 x h

max

2 x h

max

90

°

Upstream water

Downstream water

5 cm

k

3 cm

45

°

k

3 cm

>>