Set-up, parameter adjustment – VEGA VEGAMET 514… D User Manual

Page 34

Advertising
background image

34

VEGAMET 514… D

Set-up, parameter adjustment

Parameter adjustment MST2, processing (flow)

With the scaling of MST2 the conditions for the signal
conditioning instrument is provided to calculate the
flow volume/time. The respective values for min. and
max. flow are generally stated by the flume
manufacturers or can be calculated as proximity

values (see page 29 … 32).

In case of calculation the value of min. flow is
unimportant.

Example relating to a rectangular flume (see page
31):

- Max. flow 1385 m

3

/h

- Min. flow 4,4 m

3

/h

Parameter adjustment MST2, processing (flow)

–– Scaling

–– 0 % corresponds to

0

Range 0 … (4) … 9999 (Min. flow)

–– 100 % corresponds to

1000

Range 0 … (1385) … 9999 (Max. flow)
This value (1385) is automatically transferred to the

menu point "Pulse parameter volume", see page 36
and 41.

–– Decimal point

888.8

.8888

–– relating to

flow

–– Unit

L/s

etc. choice adapted to flow measurement

–– Linearization curve

linear

Given curves for flumes and

Root funct.

series

Venturi

Palmer-Bowlus
Quadrant

V-Notch

Trapezoidal weir

Rectangular overflow

Lin.curve 1

Enquiry of three curves to be edited

Lin.curve 2

Editing see page 43

Lin.curve 3

After a scaling or linearization the requested output must be coordinated to the scaled or linearized
value in the menu range "Parameter adjustment outputs", see menu points "relating to" and "Unit".

–– Integration time

0 s

Range 0 … 600 sec.

100 %

^ 1385 m

3

/h

4,4 m

3