Set-up, parameter adjustment – VEGA VEGAMET 514… D User Manual

Page 40

Advertising
background image

40

VEGAMET 514… D

Set-up, parameter adjustment

Monitoring

The following requirements must be met for activation of the monitoring:

- Determine input 4 in the menu range "Configuration meas. point".
- Connect a key word (opener) to input 4 (see page 14).
- Select for the concerned relay the mode monitoring in the menu range "Parameter adjustment relay outputs"

(see page 37).

The selected relay is engergized. By pushing the key switch (opener opens) the respective actual measured
value is first of all frozen and derived thereof the relay de-energizes if the value is decreased (low) or
exceeded (high).

See additional diagram "Configuration meas. points" page 21.

–– Relay output 1 (continuation 3)

–– Kind Monitoring

With the enquiry "Monitoring" the menu point

"Monitoring on" is released.

–– Monitoring on

High

The relay of relay output 1 de-energizes when

the %-value stated under High is exceeded.

Low

The relay of relay output 1 de-energizes when

the %-value stated under Low is decreased.

High and
Low

The relay of relay output 1 de-energizes when
the %-value stated under High and Low is
exceeded or decreased.

–– Low

-5 %

Range and unit acc. to the selection in the menu

–– High

7 %

points "relating to" and "Unit", see page 34.
–5 % and 7 % are exemplary values, relating to
above diagrams.

Relay outp.

High
frozen

meas.value

d b z

t

%

Key

switch

d b z

t

%

Relay outp.

Key

switch

frozen

meas.value
Low

d b z

t

%

Relay outp.

High

Key

switch

Low

frozen

meas.value

>>