VEGAMET 514… D

Mounting

2 Mounting

2.1 Mounting versions

VEGAMET 514 D … 514 VD signal conditioning
instruments can be either mounted with a module in
a carrier BGT 596 or BGT 596 Ex.M or in a single
housing type 505 or type 506.

Module

Multipoint connector DIN 41 612, series F, 33-pole
(d, b, z) with coded pins and mounting material for
mounting in carrier BGT 596 or BGT 596 Ex.M.

Module Ex

Multipoint connector DIN 41 612, series F, 33-pole
(d, b, z) with coded pins, Ex-separating chamber
and mounting material for mounting in carrier

BGT 596 Ex.M.

Single housing

Plastic housing type 505 or type 506 for single
mounting of signal conditioning instruments with a

width of 5 TE (25,4 mm).

Mounting carrier

Mount the respective module (standard or Ex-
version) in the carrier. Wire the connections of the
multipoint connector according to the wiring plan on
page 14.

The multipoint connector is available as follows:
- Wire-Wrap standard connection 1,0 x 1,0 mm
- plug connection 2,8 x 0,8 mm
- Termi-Point Standard connection 1,6 x 0,8 mm
- soldering connection

- screw terminals 2 x 0,5 mm

2

For further information concerning mounting see
operating instruction of the carrier.

Mounting single housing

You can either screw the housing socket directly to

the mounting plate or plug on a carrier rail
(TS 35 x 7,5 acc. to EN 50 022 or TS 32 acc. toEN
50 035). Connect the terminals according to the
wiring plans on the following pages. For further
information to the mounting see operating instruction

of the housing.

Transparent cover

To protect the housing against unauthorized
operation, the front plate of VEGAMET can be
provided with a lockable transparent cover.

Coding

To avoid interchanging of the various signal
conditioning instruments, the multipoint connector of

the carrier or the housing is provided with pins and
the multiple plug of the signal conditioning
instrument with holes (mechanical coding).

An Ex-coding with fixed coded pin ensures that not-

Ex and Ex-instruments are not interchanged.

An instrument coding ensures that the various signal
conditioning instruments are not interchanged. The
respective coded pins are attached to each module

or housing. Provide the multipoint connector with
these coded pins acc. to the following schedule and
figure.

Instrument

Ex-

coding

coding

VEGAMET 514 D

a5 / c5

VEGAMET 514 D Ex

a5 / c5

c23

VEGAMET 514 VD

a7 / c5

Fig. 2.1 Coding schedule

Instrument coding

Function coding

o 9 o

z b d

o 1 o

a c

a5

a7

c23

o 3 o

o 5 o

o 7 o

o11o

o13o

o15o

c5

o17o

o19o

o21o

o23o

o25o

o27o

o29o

o31o

VEGAMET

Ex-coding

514 D

514 VD

Fig. 2.2 Module coding, VEGAMET