VEGA VEGAMET 514… D User Manual

Page 36

Advertising
background image

36

VEGAMET 514… D

Set-up, parameter adjustment

Parameter adjustment MST1 and MST2, outputs

Current output 3 (continuation)

–– Pulse parameter

–– Volume

1000

Range 0 … 9999

–– Quantity x factor

1

Multiplication factor x1, x10, x100, x1000

–– Creeping quantity

suppression

0 %

Range 0 % … 100 %

–– Sampling

h 1

Range 1 … 100 h (hours)
This menu point is only displayed in mode "Sampling
output".

–– Volt outputs

–– Volt output 1

acc. to basic configuration coordinated to MST1, i.e. 0 … 10 V relating
to level

–– relating to

Percent

etc. choice acc. to list

–– Current output

2/10 V

0/10 V
10/2 V

10/0 V

-free-

activates the menu points "Current at 0% and 100%"

–– Volt at 0 %

2 V

adjustable range 0.0 … 10.0 V

–– Volt at 100 %

10 V

adjustable range 0.0 … 10.0 V

Reaction of the volt output in case of failure

–– at failure

0 V

0 V

11 V

11 V

--

Actual value is kept

0 %

Volt value relating to 0 %

100 %

Volt value relating to 100 %

–– Volt output 2

as volt output 1, however acc. to basic configuration

coordinated to MST2, i.e. 0 … 10 V relating to flow.

Volt output 2 can be configured to level like volt output 1.

–– Volt output 3

as basic configuration coordinated to no MST (– –).

Advertising