4 mounting, 1 general instructions, 2 mounting instructions – VEGA VEGAMET 391 4 … 20 mA_HART User Manual

Page 10

Advertising
background image

10

4 Mounting

VEGAMET 391 • 4 … 20 mA/HART

36032-EN-130701

4 Mounting

4.1 General instructions

The instrument is designed for recessed installation in an instrument

panel, housing front plate or a switching cabinet door. The required

cut-out is 92 x 92 mm (3.63 x 3.63 in) according to EN 60529. When

installed correctly, protection rating IP 65 is guaranteed. As an

alternative, the instrument can be mounted in a switching cabinet or

protective housing by means of four screws (fixed with screws on rear

of housing). A mounting adapter for carrier rail mounting is available

as an option (top hat rail 35 x 7.5 according to DIN EN 50022/60715).
Note:

If the instrument is mounted via the screws or carrier rail, it must

always be inside a switching cabinet or protective case.
A VEGAMET 391 in Ex version is an auxiliary, intrinsically safe instru-

ment and may not be installed in explosion-endangered areas.
Before setup, the Ex separating wall must be attached to Ex versions.

Safe operation can only be ensured if the operating instructions

manual and the EC type approval certificate are observed. VEGAMET

391 must not be opened.

4.2 Mounting instructions

1. Make sure that the cut-out required for mounting has a size of

92 x 92 mm (3.63 x 3.63 in).

2. Check for the correct position of the seal directly behind the front

plate and insert the instrument from the front into the front panel

cut-out.

3. Press the two tensioning elements into the provided gaps.
4. Screw in the two screws of the tensioning elements evenly with a

screwdriver.

Installation possibilities

Front panel mounting

Advertising