VEGA VEGAMET 391 4 … 20 mA_HART User Manual

Page 21

Advertising
background image

21

6 Setup with the integrated display and adjustment unit

VEGAMET 391 • 4 … 20 mA/HART

36032-EN-130701

VVO protocol: Direct standard connection between signal condi-

tioning instrument and PC for parameter adjustment and enquiry

(e.g. with PACTware and DTM)

PPP: Dial-up connection between signal conditioning instrument

and modem for independent transmission of e-mails (dial-out con-

nection) or enquiry via web browser (dial-in connection)

ASCII protocol: Direct standard connection between signal con-

ditioning instrument and PC for enquiry with terminal programs,

e.g. Hyperterminal

Carry out your settings via the respective keys and save with

[OK]. Further information is available in the supplementary

instructions manual "RS232/Ethernet connection" and the online

help of the respective DTM.

With instruments with integrated RS232/Ethernet interface, the date

and time can be entered in this menu item. These time settings are

buffered in case of voltage loss via a capacitor as well as as battery

up to 10 years.

Carry out your settings via the appropriate keys and save with

[OK].

The VEGAMET 391 can process measured values from 4 … 20 mA/

HART sensors via analogue communication as well as via digital

HART protocol.
Analogue 4 … 20 mA transmission

In the standard setting of VEGAMET 391 the measured value trans-

mission is carried out via analogue 4 … 20 signal. An adjustment in

the sensor influences directly the input variable of VEGAMET 391.

Only carry out the adjustment on one instrument, either on VEGAMET

391 or on the sensor. The adjustment in VEGAMET 391 is always car-

ried out in mA (analogue transmission).
Digital HART transmission

For transmission via HART, VEGAMET 391 must be informed which

sensor value should be used for further processing. Depending on

the sensor type, this can be distance, pressure or temperature. With

all HART sensors, the unchanged initial value of the sensor is always

transmitted to VEGAMET 391. Thus, adjustment must always be car-

ried out on VEGAMET 391, never on the sensor. Different parameters

and measuring units are available.
When HART sensors from other manufacturers are connected, the

options PV (Primary Value) and SV (Secondary Value) are available.

Device settings - Date/

Time

Measurement loop - Input