Input type

Passive

Switching threshold

Ʋ Low

-3 …5 V DC

Ʋ High

11 …30 V DC

Max. input voltage

30 V DC

Max. input current

30 mA

Max. sampling rate

10 Hz

Relay outputs
Quantity

6 x operating relay

Function

Switching relay for level, fault signal or pulse relay for

flow/sampling pulse

Contact

Floating spdt

Contact material

AgSnO2, hard gold-plated

Switching voltage

min. 10 mV DC, max. 250 V AC/60 DC

Switching current

min. 10 µA DC, max. 3 A AC, 1 A DC

Breaking capacity

min. 50 mW, max. 500 VA, max. 54 W DC (with U less

than 40 V)

1)

Min. programmable switching hysteresis 0.1 %
Mode pulse output

Ʋ Pulse length

350 ms

Current output
Quantity

1 x output

Function

Current output for level or flow/sampling pulse

Range

0/4 … 20 mA, 20 … 0/4 mA

Resolution

1 µA

Max. load

500 Ω

Fault signal (switch over)

0; < 3.6; 4; 20; 20.5; 22 mA

Accuracy

Ʋ Standard

±20 µA (0.1 % of 20 mA)

Ʋ with EMC interferences

±80 µA (0.4 % of 20 mA)

Temperature error relating to 20 mA

0.005 %/K

Mode pulse output

Ʋ Voltage pulse

12 V DC at 20 mA with load 600 Ω

Ʋ Pulse length

200 ms

USB interface

2)

Quantity

1 x on front plate

Plug connection

Mini-B (4-pole)

USB specification

2.0 (Fullspeed)

Max. cable length

5 m (196 in)