5 flow measurement – VEGA VEGAMET 391 4 … 20 mA_HART User Manual

Page 47

Advertising
background image

47

8 Application examples

VEGAMET 391 • 4 … 20 mA/HART

36032-EN-130701

8.5 Flow measurement

For flow measurement in open flumes, a constriction or standardised

flume must be used. Depending on the flow volume, this constriction

generates a certain amount of backup. The flow can be determined

from the height of this backup. The flow volume is outputted by an ap-

propriate number of pulses on the relay or current output and can thus

be further processed by connected downstream instruments.
There is also the possibility to sum up the flow volume by means of a

totalizer, the result is available on the display and as PC/DCS value.

Depending on the type and version, each flume generates a different

backwater. The data of the following flumes are available in the instru-

ment:

Palmer-Bowlus-Flume

Venturi flume, trapezoidal weir, rectangular weir

Rectangular weir, V-Notch

Setup

The configuration of the flow measurement loop requires PACTware

with the suitable DTMs. The example refers to a flow measurement

with a radar sensor. The following setup steps must be carried out:

Selection of the parameter "Flow"

Carrying out adjustment

Select flume (linearization)

Set scaling

Parameter adjustment of pulse outputs

Parameter adjustment of the totalizer

Select in the DTM window "Parameter" the option "Flow" with the

requested unit of measurement.

Min. adjustment: Enter the suitable value for 0 %, i.e. the distance

from the sensor to the medium as long as there is no flow. These are

in the following example 1.40 m.
Max. adjustment: Enter the suitable value for 100 %, i.e. the distance

from the sensor to the medium, with the max. flow volume. This is

0.80 m in the following example.

100%

0,80m (d)

=

400m

3

/h

=

0%

1,40m (d)

=

0m

3

/h

=

Fig. 19: Adjustment of flow measurement with V-notch

Functional principle

Flume

Parameter - Flow

Adjustment

Advertising